/****************************************************************/ /* RELEASE NOTES */ /****************************************************************/ - Important note : * Backward compatibility is affected since versions starting with "06." Versions "06." have a new firmware signature which is checked for all future firmware upgrades It is not possible to downgrade below "06." due to this difference * About IT equipment management (also called "Device"): . When creating or modifying an IT equipment, all ePDUs that are involved must be reachable and all persistent measures are reset. . In order to keep a consistent configuration, it is safer to delete all IT equipment using a given ePDU before disconnecting it from the daisy chain. . All persistent measures of a piece of IT equipment are reset when a "Data" or an "ePDU" configuration file is uploaded. . All concerned ePDU device must be present when uploading a "Data" or an "ePDU" configuration file. * SSL is supported with up to 4 units in daisy chain. * In a Daisy chain configuration, all ePDUs must be of the same type (all Managed, or all Metered Input, ...) and with the same number of input. * In a Daisy chain topology, each ePDU must use the same major firmware version. - Limitations : * Running several supervision software agents simultaneously can prevent mass-configuration and mass-upgrade features to run properly. * Using FTPS protocol with DaisyChain units can prevent upgrade feature to run properly. * Using SSL protocol with Managed PDUs connected in a Daisy Chain can induce some performance issues. * Using SSL protocol with 2048 bits key length can induce some performance issues. /================================================================/ Project : Eaton G3 ePDU firmware /================================================================/ /================================================================/ Firmware Version: 06.00.0003 - Sep 28, 2023 Changes since previous version : -------------------------------- - Web pages version 02.00.0049 - SHA2:60ef373ea56fb8f99da0829574ee593e84ee0279f8d580650f2c2bfdb4d0301e - New feature: * LDAP TLS Version supporting only 1.0 now it supports 1.0,1.1,1.2 - Update: * NA - Fixed issues: * Password Complexity issue solved- All users can change password to complex. * CLI put password complexity compulsion on super admin and not others * No password complexity is applicable to LDAP and Radius users - Known issues: * NA - Important note: * Backward compatibility is affected since version starting with "06." Versions above 06.00.0001 are signed Not possible to downgrade below "06." * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 06.00.0002 - Aug 21, 2023 Changes since previous version : -------------------------------- - Web pages version 02.00.0048 - SHA2:a0f15ac295aa7e79d3729f52c9a593b777c494f6813d5732b503b99616a7ae39 - New feature: * removed Intermediate step while uploading signed firmware over unsigned firmware * accept only signed firmwares (No downgrade compatiblity) - Update: * NA - Fixed issues: * NA - Known issues: * NA - Important note: * Backward compatibility is affected since version starting with "06." Versions above 06.00.0001 are signed Not possible to downgrade below "06." * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 06.00.0001 - April 18, 2023 Changes since previous version : -------------------------------- - Web pages version 02.00.0048 - SHA2:4ea1be4cda8038c6f85f2147a7e58bd1c06633e44d6b092041f74b7d416ae784 - New feature: * Firmware signature implemented - Update: * SNMPv3 supports SHA AES128 by default, and can be manually changed to MD5 DES via command-line for backward compatibility - Fixed issues: * When we restore PDU if password is complex, PDU will not give "Change password" pop up - Known issues: * NA - Important note: * Backward compatibility is affected since version starting with "06." Versions above 06.00.0001 are signed Not possible to downgrade below "06." * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 05.03.0000 - Nov 21, 2022 Changes since previous version : -------------------------------- - Web pages version 02.00.0047 - SHA2:c26f8d8fb3275731ba87a7c6821d3118fd7300fc71bcda7ff66d0c5e1b263c0a - New feature: * Updated the SSH library to NanoSSH 6.5.2, Weak SSH Ciphers removed * Password change at login when fail the password complexity rule for webpages as well as CLI * LCD pin activation and USB enable disable option on log in window if password is not complex * Updated Quadnet lib to 6.0.1.78 * AES/SHA support for SNMPv3 * Password reset from Serial, user should no if password is not complex - Update: * NA - Fixed issues: * NA - Known issues: * NA - Important note: * Backward compatibility is affected since version starting with "05." To downgrade to a previous version, it is mandatory to first downgrade to the 04.04.0000 version before downgrading another version. * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 05.02.0000 - July 07, 2022 Changes since previous version : -------------------------------- - Web pages version 02.00.0046 - SHA2:cfaf09f3270ceada004f8a68845fe2dc06260051b22bed356423acb9f567f8f0 - New feature: * Kraken - InputPlugType (OID : 1.3.6.1.4.1.534.6.6.7.3.1.1.8) value 400 is implemented * Kraken - Bad alarm with no description is removed * Kraken - UCF change so that Edelweiss and SCOB UCFs can coexist * Kraken - Universal input - Manual setting for 3P Wye / 3P Delta - Update: * NA - Fixed issues: * NA - Known issues: * NA - Important note: * Backward compatibility is affected since version starting with "05." To downgrade to a previous version, it is mandatory to first downgrade to the 04.04.0000 version before downgrading another version. * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 05.01.0002 - May 12, 2022 Changes since previous version : -------------------------------- - Web pages version 02.00.0045 - SHA2:bc61b5f7214916ae9bea324679746ab7a3a50274f5f987f59f6b382890f6d5c5 - New feature: * NA - Update: * NA - Fixed issues: * "Internal error" logging issue has fixed - Known issues: * NA - Important note: * Backward compatibility is affected since version starting with "05." To downgrade to a previous version, it is mandatory to first downgrade to the 04.04.0000 version before downgrading another version. * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 05.01.0001 - May 04, 2022 Changes since previous version : -------------------------------- - Web pages version 02.00.0045 - SHA2:f407dd241ff8bed9f019d35329c27ab99c555a9a7d8414f8bd688184d2998cc7 - New feature: * In HTTPS mode, the polling of restricted PDU daisy chained ([4], [5], [6] and [7]) are stopped. - Update: * NA - Fixed issues: * Trap signals received on MIB browser from PDU for sensor EMP02 - Known issues: * Internal error is getting log when we log out and log in again on HTTPs with daisy chain - Important note: * Backward compatibility is affected since version starting with "05." To downgrade to a previous version, it is mandatory to first downgrade to the 04.04.0000 version before downgrading another version. * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 05.01.0000 - Jan 21, 2022 Changes since previous version : -------------------------------- - Web pages version 02.00.0044 - SHA2:2fdb9631b0f9ef0f02585b56dd56339e7185f547fdde05d3e349040cf7811f36 - New feature: * HTTPS option enforced over HTTP by default Daisy chain Implemented with (1+3) PDUs limitations in HTTPs Web pages also updated for daisy chain On LCD SSL restricted message has implemented * Manage password complexity to have serial number as password * Impossible to upload SSL certificate file upper than 4096 bytes, but it does not hang PDU now (Logs updated) - Update: * Update the TCP/IP Stack to version 6.0.1.74 - Fixed issues: * Redundant sentences removed from messages while password setting * User cannot bypass EULA acceptation by doing a refresh (F5) of the web page * User logging cleaning - Known issues: * NA - Important note: * Backward compatibility is affected since version starting with "05." To downgrade to a previous version, it is mandatory to first downgrade to the 04.04.0000 version before downgrading another version. * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 05.00.0000 - July 15, 2021 Changes since previous version : -------------------------------- - Web pages version 02.00.0043 - SHA2:d1f2a955835984f9c81d99c88aa9be61696eac438c333aca14b820cc92b9d733 - New feature: * Support 100A functionality * Implement a saturation mechanism for measurements * Implement a fixed password complexity for users password: + 1 Upper case, 1 Lower case, 1 special character, 8 char minimum length * Password brute force protection and add a log when user is blocked * USB mode can be activated/deactivated by the SuperAdmin * Provide a file that allows the user to check the integrity of the firmware upgrade package * UI developed for EULA and login page * Restrict FTP/S access to only upgrade, logs in Read-only, configuration and UCF - Update: * Update the TCP/IP Stack to version 6.0.1.72 * Update XML library to version 2.2.10 * Remove EnergyWise protocol * Update log information and add some new logs - Fixed issues: * Fix some security vulnerabilities - Known issues: * Log message is not up to date for the FTP interface * Create a Hostname more than 15 characters, the DHCP lease doesn't work correctly - Important note: * Backward compatibility is affected since version starting with "05." To downgrade to a previous version, it is mandatory to first downgrade to the 04.04.0000 version before downgrading another version. * It is recommended to verify the integrity of the upgrade package by comparing the hash value of this package with the one provided /================================================================/ Firmware Version: 04.04.0000 - February 18, 2021 Changes since previous version : -------------------------------- - Web pages version 02.00.0041 - New feature: * Recover the configuration files after a downgrade to this version - known issues: * The log file is reset during a downgrade to this version - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.03.0001 - September 30, 2020 Changes since previous version : -------------------------------- - Web pages version 02.00.0041 - New feature: * Fix the Daisy Chain communication lost issue * Add a flag to manage the compatibility between versions - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.03.0000 - July 09, 2020 Changes since previous version : -------------------------------- - Web pages version 02.00.0041 - Update: * Update the TCP/IP Stack to version 6.0.1.67 * Remove weak SSH algorithms - Fixed issues: * Fix Ripple20 vulnerabilities * Fix Vulnerability Birthday attacks against TLS ciphers with 64bit block size * Fix vulnerability ReadOnly users could make changes - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.02.0001 - February 10, 2020 Changes since previous version : -------------------------------- - Web pages version 02.00.0041 - Fixed issues: * Fixed the SNMPV3 issue which no longer worked * Fixed an issue when the imported SSL certificate file was greater than 4096 bytes * Fixed an issue when the superadmin user login was not reset during a recovery password - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.02.0000 - January 15, 2020 Changes since previous version : -------------------------------- - Web pages version 02.00.0041 - New feature: * An user can import their own SSL certificate and private key * Display the PDU name on LCD, if it is different than the default one - Update: * Update the TCP/IP Stack to version 6.0.1.60 * Upgrade the SSH key to RSA 2048 * Restrict only to TLS1.2 * Remove unsecure SSL ciphers * New method to define the default value of the voltage thresholds * Change the password reset behavior on serial connexion - Fixed issues: * Fixed an issue when saving an Ipv6 address on the Web pages * Fixed an issue when the value of the input type is greater than 255 * Fixed an issue on the default value of the gang voltage threshold on a Delta ePDU - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.01.0003 - November 28, 2019 Changes since previous version : -------------------------------- - Web pages version 02.00.0040 - Fixed issues: * Fixed PHY Ethernet timeout issue which may fail the Ethernet communication in AutoNeg mode * Fixed SNMP issue when the size of a string was multiple of 4 * Fixed SNMP issue when the size of a string was 32 - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.01.0002 - September 6, 2019 Changes since previous version : -------------------------------- - Web pages version 02.00.0040 - Fix issues: * Fixed SNMP/TRAP issue when the temperature value does not match with the oid of the temperature unit * Fixed the communication loss issue for all TCP protocols (HTTP, FTP, SSH, ...) - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.01.0001 - August 23, 2019 Changes since previous version : -------------------------------- - Web pages version 02.00.0040 - Add new CLI command to read PHY registers - Fix issues: * Fix issue in SNMP when only 6 sensors are handled in DaisyChain - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.01.0000 - July 19, 2019 Changes since previous version : -------------------------------- - Web pages version 02.00.0040 - Add new outlet type SDG400 - Add Russian language on Web pages - Don't display the LCD popup when a USB stick is plugged if the LCD password is activated - Full compatibility with the Mass Commissioning tool - Fix issues: * Fix "Sometimes disconnect the Usb cable doesn't work" * Fix "Change the Mass Commissioning passphrase twice doesn't work" * Fix "In CLI, the discover command doesn't work when no sensors are plugged to USB cable" * Fix "IPM could no longer change the ePDU login/password" * Fix issues on Web pages for HDMO ePDU * Fix issues on USB sensors - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.00.0002 - April 02, 2019 Changes since previous version : -------------------------------- - Web pages version 02.00.0039 - Improve USB sensor communication - Fix issues: * Fix "Bad Logs" on breakers - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.00.0001 - March 18, 2019 Changes since previous version : -------------------------------- - Web pages version 02.00.0039 - Fix issues: * Fix "Sometimes USB sensors are not discovered" * Fix "Sensor Identification updated after up to 10 minutes" * Fix "Missing log dry-contact status changes" * Fix "Make Serial Console work when USB sensor plugged" * Fix "Unexpected message in the log in USB menu" * Fix "The Eaton Epdu MIB does not respond anymore by SNMP" * Fix "Bad alarms on the Daisy chain" - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 04.00.0000 - March 08, 2019 Changes since previous version : -------------------------------- - Web pages version 02.00.0039 - New feature: USB sensor Daisy Chain (3 max) * EMPDT1H1C2 sensor compatibility * New Eaton sensor MIB integrated * Update the Environment LCD menu * Manage the switch between the serial sensor and the USB sensor - Light Mass commissioning feature integrated - known issues: * Daisychain communication may send wrong information or alarm - Important note: * Backward compatibility is affected since version starting with "04.": In daisyChain topology, each ePDU must use the same major firmware version. /================================================================/ Firmware Version: 03.01.0002 - September 26, 2018 Changes since previous version : -------------------------------- - Web pages version 02.00.0038 - Fix Gang Voltage CLI issue - known issues: * Profile Read/Write users are not able to modify the card system parameters * Communication lost on HD daisy chained PDU (set as Device) when lot of alarms are ON and after an electrical restart. /================================================================/ Firmware Version: 03.01.0001 - September 19, 2018 Changes since version 03.01.0000: --------------------------------- - Web pages version 02.00.0038 - Add a mask in the command Relay sent to the measurement cards - Add a new LCD menu to set the speed/duplex of the Ethernet link - Add a specific label according the type of ePDU (G3 or G3 High Density ePDU) - Add new logs when communication with mesaurement cards has been lost - Fix the following issues: * Fix issue when card reboot unexpectedly * Missing label title for the Admin settings * Missing unit for Neutral current on Web pages * Blank Web page is displayed with IE11 browser * Change Feed name label * Improve Overview display of Web pages for 1-ph G3 High Density ePDU * Fix issue when Device are in communication lost when the card reboots - Important note: * Backward compatibility is affected since version starting with "03." To downgrade to a previous version, it is mandatory to first downgrade to the 02.00.0054 version before downgrading another version. /================================================================/ Firmware Version: 03.01.0000 - July 03, 2018 Changes since version 03.00.0001 : ---------------------------------- - Web pages version 02.00.0037 - Add the Feed name field in the Web pages - New feature for High Density ePDU * Web pages are able to display up to 54 outlets * On Web pages/overview picture, outlets are sorted by phase * Add a new option which keeps the outlet relays in the current position when the HD ePDU is powered down * Add the new input neutral current measure for a wye ePDU * Add new OID: + systemType + outletAutomaticShutoff - Fix the following issues : * Complete the description for the OID unitType * Fixed issue when the PDU Serial Number is missing for a High Density ePDU * Fixed issue when the Crest Factor measurement is 0 * Fixed issue when the Part number is cut on the LCD - Important note : * Backward compatibility is affected since version starting with "03." To downgrade to a previous version, it is mandatory to first downgrade to the 02.00.0054 version before downgrading another version. /================================================================/ Firmware Version: 03.00.0001 - May 03, 2018 Changes since version 03.00.0000 : ---------------------------------- - Web pages version 02.00.0036 - Fix issue on the Mutex File System - Fix issue with the non-operational licenses link - Important note : * Backward compatibility is affected since version starting with "03." To downgrade to a previous version, it is mandatory to first downgrade to the 02.00.0054 version before downgrading another version. /================================================================/ Firmware Version: 03.00.0000 - April 13, 2018 Changes since version 02.00.0054 : ---------------------------------- - Web pages version 02.00.0035 - Implement a new strong password encryption - Check the user's privileges changing a setting - Update SSH library - Update microprocessor library - Add LCD logo for a specific customer - According the platform, display the last sent command or the relay feedback - Handle the startup of the ePDU according the platform - Handle the hardware configuration file according the platform - Provide a new object to identify the platform - Resolved Issues : * Fixed the Radius CVE-2017-10979 - Important note : * Backward compatibility is affected since this version. To downgrade to a previous version, it is mandatory to first downgrade to the 02.00.0054 version before downgrading another version. /================================================================/ Firmware Version: 02.00.0054 - March 9, 2018 Changes since version 02.00.0053 : ---------------------------------- - Web pages version 02.00.0035 - Read new password encryption method - Automatic baud rate detection with the measurement cards - Increase breaker voltage threshold to 50V - Update hash table library - Update XML library /================================================================/ Firmware Version: 02.00.0053 Changes since version 02.00.0052 : ---------------------------------- - Web pages version 02.00.0035 - An user must be re-authenticated to change an user password - Radius: the send of the Service-Type Attribute is optional - Improve the way to calcul the Total Energy - Fix the following issues : * Potential memory leak with DHCP auto config settings /================================================================/ Firmware Version: 02.00.0052 Changes since version 02.00.0051 : ---------------------------------- - Web pages version 02.00.0034 - Fix potential issue in production process /================================================================/ Firmware Version: 02.00.0051 Changes since version 02.00.0050 : ---------------------------------- - Web pages version 02.00.0034 - Mask password parameters in Telnet/SSH - SSH activated by default - The customized dry contact name is carried through to the alarms webpage and LCD. - At the ePDU startup, set an outlet directly to ON if the startup timer parameter is set to 0 - Add a new type of outlet: "SDG300" - IPM-Infra interoperability * Add new object "PDU.Inputx.iName", the friendly name of input. * Add new OID: + inputPhaseDesignator + groupDesignator + outletDesignator + groupColor + inputFeedName + inputFeedColor + groupInputIndex + outletPhaseId + inputPowerCapacity - Fix the following issues : * Fix issue on 3-Ph when get SNMP returns always 0 with "inputCurrentCapacity.0.1.2" value * GANG measures in SNMP for EMAB20 et EMOB20 G3 ePDU /================================================================/ Firmware Version: 02.00.0050 Changes since version 02.00.0049 : ---------------------------------- - Web pages version 02.00.0033 - Remove the client ID in the DHCP request. /================================================================/ Firmware Version: 02.00.0049 Changes since version 02.00.0048 : ---------------------------------- - Web pages version 02.00.0033 - Fix an issue on the EMOB71 PDU, 2 outlets remains off on the web pages. /================================================================/ Firmware Version: 02.00.0048 Changes since version 02.00.0047 : ---------------------------------- - Web pages version 02.00.0033 - Fix the allowed memory size exhausted error on the USB mode. /================================================================/ Firmware Version: 02.00.0047 Changes since version 02.00.0046 : ---------------------------------- - Web pages version 02.00.0033 - Fix a memory overflow when saving the configuration files on the ePDU ESW374-10. /================================================================/ Firmware Version: 02.00.0046 Changes since version 02.00.0045 : ---------------------------------- - Web pages version 02.00.0033 - Reset the settings to factory defaults, delete the configuration file previously downloaded by the DHCP auto-configuration procedure. - Reset the settings to factory defaults, the value of the DHCP auto configuration parameter is not modified if the "Keep Ip" parameter is enabled. /================================================================/ Firmware Version: 02.00.0045 Changes since version 02.00.0044 : ---------------------------------- - Web pages version 02.00.0033 - Dhcp can be set with a fallback IP address or not - Auto Configration via DHCP can be handled by option 66/67 or by Boot File Name and next-server parameters - Auto Configration via DHCP option is activated by default - Possibility to create some default parameter which can be set to a specific customer at the production /================================================================/ Firmware Version: 02.00.0044 Changes since version 02.00.0043 : ---------------------------------- - Web pages version 02.00.0032 - Add the feature SSH over Ipv6 - Correct an issue on the log measure of high critical current of a Daisychain device /================================================================/ Firmware Version: 02.00.0043 Changes since version 02.00.0042 : ---------------------------------- - Web pages version 02.00.0031 - Improve SSL performance by increasing socket buffer length - Fix potential memory corruption issue /================================================================/ Firmware Version: 02.00.0042 Changes since version 02.00.0041 : ---------------------------------- - Web pages version 02.00.0031 - Add the Auto Configuration via DHCP feature - Create new SSL certificate with SHA256 signature algorithm - Improve SSL performance by increasing socket buffer length - Fix the following issues : * Fix the issue on the Power Factor value on input2 of a Dual Input G3 ePDU. * Fix the issue where outlet control settings were not saved permanently via SNMP. /================================================================/ Firmware Version: 02.00.0041 Changes since version 02.00.0040 : ---------------------------------- - Web pages version 02.00.0030 - Compatible with Eaton G3 Dual Input ePDU - Compatible with GBCONV accessory (Gigabit Ethernet compatibility) - Fix the following issues : * Bad informations displayed in the outlet tooltips. * Phase is displayed as unknown in the outlet tooltip. * Overview, branch circuits, & Devices Web pages were broken when a branch circuit friendly name contained a double quotes. * Webpage autorefresh didn't work for daisy chained PDU on PDU[4], PDU[5], PDU[6], PDU[7] * On LCD display, add Environment menu for SW and IL ePDU type * Return the correct value for the OID inputPlugType corresponding to "PDUInput1Type" and "PDUInput2Type" /================================================================/ Firmware Version: 02.00.0040 Changes since version 02.00.0039 : ---------------------------------- - Web pages version 02.00.0029 - Fix the following issues : * Log the current value after 5s during an alarm (new feature) sometime is not running for daisy chained PDU * Log the current value after 5s during an alarm sometime is not running for 3 Phases * Unexpected pop windows displayed on LCD when user "Save eNMC file" /================================================================/ Firmware Version: 02.00.0039 Changes since version 02.00.0038 : ---------------------------------- - Web pages version 02.00.0029 - Add the possibility to copy IP settings via the USB mode - During a high critical current alarm, the value of the current is logged after 5s - Improve the Daisy-Chain interface on the home window of LCD - Fix the following issues : * Fix the SNMP issue on power factor unit * Fix the SNMP issue on input power value for a daisy chained PDU set as a Device * Fix the issue "impossible to upload a file in FTPS" when HTTP and FTPS is enabled /================================================================/ Firmware Version: 02.00.0038 Changes since version 02.00.0037 : ---------------------------------- - Web pages version 02.00.0028 - Fix the following issues : * LDAP authentication error * Login error, windows is not displayed * After a switch ON/OFF command on outlets, sometimes some outlets not switching ON/OFF * Navigation on web browser very slow when PDU daisy chained 1+7 in SSL * Outlet schedule not running on daisy chained PDU * After Restore factory default settings, Feed color parameter doesn't return to 'None' * Fix for wrong OID value for input.count on 3ph ePDU /================================================================/ Firmware Version: 02.00.0037 Changes since version 02.00.0036 : ---------------------------------- - Major improvement: * Integrate new TCP/IP Stack - Web pages version 02.00.0027 - Add FTPS (activated with 'Force HTTPS') - Add TLS 1.1 and 1.2 - Add input feed color management for gangs - Add new logs: * F/W upgrade in Daisy Chain * F/W upgrade failed * FTPS connection - Add new Daylight Saving Time mode: United States - Current and voltage hysteresis can now be modified via CLI - Network is now available once the Ethernet cable connection has been detected (avoid card reboot on 1st Ethernet cable connection) - Fix the following issues : * Enable/Disable Syslog button was not taken into account * Jumbo frames issue (Ethernet packets bigger than 1520 bytes): caused buffer overflow and card reboot * Too long file path issue when F/W upgrading with IE * HTTPS issue: recent browser updates make the HTTPS access unavailable (in order to prevent LOGJAM vulnerability) * Reboot issue for when there is some heavy data traffic in the network (reloads the watchdog after each packet processing -> prevents 'broadcast packet storm') * Correct the issue when sending the HTTP request "page not found" * Fixes the infinitive loop and restart SCOB issue when the following HTTP request "GET /\r\n" is sended * Dynamic tasks number increased from 4 to 6 (Telnet requirement) * When telnet session is closed, wait a little before to accept a new opening session * Correct the SSH close connection issue. (After about 14 SSH connexions, login was impossible) /================================================================/ Firmware Version: 02.00.0036 Changes since version 02.00.0035 : ---------------------------------- - ENMCFW-1 : Create a new screen saver sequence on the LCD - ENMCFW-5 : Control the cycle of screen saver using arrow keys (by long key press on "ESC") - ENMCFW-11 : Allow users to choose between normal LCD display and inverted background/letter colors on the LCD - ENMCFW-47 : Improve the readability of an alarm message on the LCD - ENMCFW-50 : Leads to the active alarm menu when an alert is displayed - ENMCFW-84 : Simplify access to the USB menu on the LCD - Fix an issue on Total Max current on Device Web page - Fix an issue on the test of the presence of a breaker on some ePDU - Web pages version: 02.00.0025 - Fix the JIRA tickets : SHARK-592 : Card reboot unexpectedly after a Restart SHARK-591 : Overview menu link doesn't run on Internet explorer , due to an error in java script SHARK-587 : Bad date/time displayed for active alarm on daisy chain SHARK-577 : After import of PDU data , some device are in comm lost SHARK-606 : English word not well spelt SHARK-600 : French sentence - bad syntax SHARK-599 : French error translation SHARK-597 : French translation SHARK-596 : French translation for "Time server :" SHARK-594 : French spelling SHARK-593 : Bad French spelling SHARK-567 : The PDU information panel not open automatically on the selected ePDU SHARK-563 : The sentence need to be modified (grammar) SHARK-529 : Split-phase Method #2 has incorrect PF and CF formulas /================================================================/ Firmware Version: 02.00.0035 Changes since version 01.00.0034 : ---------------------------------- - Add the IT equipment management (up to 32 devices) - Increase the Daisy Chain capability to 8 units - Allow non-consecutive id's in Daisy Chain - Broadcast of all alarms in XML (deactivable) - Support for MI units up to 64 outlets - Add a new parameter to set the switch off delay of the LCD - Fix vulnerability VU#243585: SSL/TLS implementations accept export-grade RSA keys (FREAK) - Fix vulnerability CVE-2014-3566: SSLv3 vulnerability (Poodle) - Web pages version: 02.00.0024 - Fix the JIRA tickets : SHARK-528 : Web GUI Firefox Outlet Measurement Tooltip SHARK-529 : Split-phase Method #2 has incorrect PF and CF formulas SHARK-531 : Outlet settings windows should be disabled with Read only user/admin SHARK-539 : On the TRAP Notifications settings windows, some fields are not disabled for RO users SHARK-543 : Enhancement - Increase Max Outlet Count for MI Units SHARK-544 : Orthographic error on the web interface in french language SHARK-546 : Outlet name missing SHARK-548 : Power schedule parameters not returned to their defaults values SHARK-549 : The datas of a user account previously deleted should not reappear for the new user creation. SHARK-551 : Missing unit (second) after the Reboot period value in the Outlet tooltip. SHARK-552 : Different behavior of navigation between the Groups web page and the Outlets web page with a RO user right. SHARK-553 : Bad displayed of the power schedule tooltip in French SHARK-555 : Incorrect Text URL on Webpage SHARK-562 : DC Outlets of the second ePDU can be managed with only one outlet /================================================================/ Firmware Version: 01.00.0034 Changes since version 01.00.0033 : ---------------------------------- - Fix the abnormal reboot when several alarms are triggered /================================================================/ Firmware Version: 01.00.0033 Changes since version 01.00.0032 : ---------------------------------- - Web pages version: 01.00.0023 - Fix the JIRA tickets : SHARK-524 : Unexpected reboot of the card when Environment page is opened SHARK-525 : Fix a bug where the temperature label was not displayed in the environment settings window - Other fixes: Fix the issue when the "discovery" LCD menu disappears when a USB key is plugged /================================================================/ Firmware Version: 01.00.0032 Changes since version 01.00.0031 : ---------------------------------- - Add a selector to choice a SSL key length of 1024 bits (default) or 2048 bits - Add the "delayed switch off" feature associated with an alarm - Add the HTTP port to the IP address Hyperlink - Synchronize the ePDU friendly name in all Web pages - Web pages version: 01.00.0022 - Fix the JIRA tickets : SHARK-291 : Outlet status detecting error at high temperature step of HALT test SHARK-453 : OID object doesn't exist in MIB PDU for "Enabled switching" parameter SHARK-454 : Outlet LED changes color 1-2 seconds after the outlet changes on/off state SHARK-493 : Active alarms badly displayed in Polish SHARK-500 : LCD display issue of Info menu SHARK-505 : No output after 7 days mains on off test SHARK-520 : For MO ePDU, Web show all outlets have no output - Other fixes: Fix the issue when writing the name of the interface in logs (Serial or Telnet) Fix the issue where the bootup and authentication traps are not sent In the LCD, sort the alarm history : the most recent message is displayed first On MO ePDU, fix the issue when clicking on the outlet settings hyperlink, nothing happens - Note : * Improve the performance of the card by optimizing the LCD task * Improve the SSL performance by placing algorithm in internal flash * Better support for Western Latin character sets * In web pages, suspend all refresh threads when an error message appears * Update the kernel of the card /================================================================/ Firmware Version: 01.00.0031 Changes since version 01.00.0029 : ---------------------------------- - Update the default value for Energywise parameters - Web pages version: 01.00.0020 - Fix the JIRA tickets : SHARK-485 : Energywise : bad level value displayed for outlet status. - Other fixes: Fix the issue where the last known state ON is not applied when 2 PDU power cycle are close. - Note : * The Power Factor measure can be negative. * Russian language is not yet available. /================================================================/ Firmware Version: 01.00.0029 Changes since version 01.00.0027 : ---------------------------------- - Add power schedule feature - Add Gang colors feature - Update the SSL and SSH key length to 2048 bits. - Web pages version: 01.00.0020 - Fix the JIRA tickets : SHARK-409 : Card reboot unexpectedly during a walk on MIB-2 (RFC1213) SHARK-440 : For any new orientation of the LCD screen, the screen is redrawn. SHARK-450 : Bad calculation of section Apparent Power and PowerFactor when the Gang type is 2 or 6 (split-phase). SHARK-468 : Populate the pdu2OutletCurrentRating data in the Mib CPQPower. SHARK-470 : Outlet identification badly displayed SHARK-474 : In the device information (Daisy Chain) screen, the position of objects has been redefined. SHARK-483 : After a set string command, all other commands were ignored during a delay of 5 s. - Other fixes: Fixed an issue in the body of the email to take into account the correct type of ePDU. Fixed an issue on default current threshold values when launching a request for an outlet from a slave ePDU. Fixed the breaker error issue: In web pages, outlets appears OFF if the breaker is tripped (even if the relay of the outlet is ON). - Extra improvments: If DHCP enabled then IP addresses are not settable in LCD and CLI. Measures settings & switching settings : each threshold and parameter has its own "Apply" button. Add a log when the SuperAdmin password was recovered on serial connection. Only PDU of the same type can be daisy chained. Display real colors, the outlet id label and the gang id label defined in the UCF file. Reactivation of the alarms history on LCD. Secure against too long text passed in the URL command. Improve the LDAP test feature. Improve the error feedback when setting any value on Web pages. The password of the LCD must be a number of exactly 4 digits. Adjust the LCD contrast for a better display. - Note : * The Power Factor measure can be negative. * Russian language is not yet available. /================================================================/ Firmware Version: 01.00.0027 Changes since version 01.00.0026 : ---------------------------------- - Add managed basic features - Add Cisco EnergyWise feature - Add LDAP authentication test - Apparent Power, Reactive Power and Active Power size in HID database change to 4 bytes. - Fixed an issue in the display of Percent Load on web pages. - Compatible with "ePDU G3 In-Line Metered" PDU type - Web pages version: 01.00.0018 - Fix the JIRA tickets : SHARK-374 : NO change in time for daylight saving time enable/disable. SHARK-59 : Outlets Breakage reporting problem. SHARK-300 : CLI object for MA PDU error. SHARK-430 : Impossible to open a session with local ePDU user (access right R/W) if an IPM is already managing this ePDU. SHARK-284 : Outlet power reboot periode set to 0 & Reboot action AND Group reboot -> shut off outlets. SHARK-361 : HTTPS > Factory reset/ restart > Logs > Wrong description log it generates. SHARK-429 : Card doesn't stop sending report emails evry one minute. SHARK-297 : Communication lost during SNMP endurance / outlet sequence / MA 3+1 /SSL Chrome. SHARK-390 : Alarms info difference between "Logs" and "Active alarms" in burn in test. SHARK-438 : Message can mislead the user when the user (ePDU user) tries to open a session already open on another browser. SHARK-439 : In Ports Settings (menu : Security > Global), no warning message if the user disables all the network protocol (HTTP / Console /FTP). SHARK-435 : Max Current Occured On date not updated. SHARK-436 : Calendar for the 'Date of next report' is not synchronized with the date/time of the card. SHARK-437 : Values in the sensor settings windows are not centered (display) in columns. SHARK-420 : Activation of LCD password doesn't run. - Note : * The Power Factor measure can be negative. /================================================================/ Firmware Version: 01.00.0026 Changes since version 01.00.0025 : ---------------------------------- - Improve the mass config and mass upgrade with IPM feature - When uploading the configuration data file, don't duplicate the IPv4 and IPv6 addresses - Web pages version: 01.00.0017 - Fix the JIRA tickets : SHARK-391 : Alarms "Internal error" in logs for Daisy chain test. SHARK-399 : Outlet states display abnormal on "Overview". SHARK-401 : Upgrade in SSL mode sometime doesn't run when an IPM is supervising the ePDU. SHARK-404 : Bad outlet status displayed on Overview page. SHARK-406 : Card reboot unexpectedly during a night endurance. SHARK-410 : The Reset Max current on a branch circuit does also a reset of dates on all other branches of the PDU. SHARK-413 : Impossible to display Overview, Groups and Outlets web pages after updating an outlet label with single quote character. SHARK-414 : In RADIUS Web pages, disabled the Save button when session is opened with an admin user in Read Only access. SHARK-415 : In Web pages, the translation of the tooltip associated with the delete button is missing. SHARK-416 : The "Default" button not placed at the same place between two web pages. /================================================================/ Firmware Version: 01.00.0025 Changes since version 00.00.0024 : ---------------------------------- - Add the mass config and mass upgrade with IPM feature - Standardization of the login length to 31 characters - Length of Trap and Snmp community name is now at 24 characters - Minor modifications in the MIB - Improve the Daisy Chain communication - 1 more Language: Italian. - Web pages version: 01.00.0016 - Fix the JIRA tickets : SHARK-244 : IPv6 local address is not displayed. SHARK-246 : User has no alarm if PDU daisy chain host lost communication with the device. SHARK-252 : Time is not synchronised in Daisy chain. SHARK-253 : In Web pages, the "restore factory default settings" removes the Daisy Chain configuration. SHARK-258 : Unplugging the PDU creates a "Low Voltage" event. SHARK-293 : No message displayed without Ethernet link. SHARK-295 : In case of alarms with 2 levels, critical alarm is not removed from list when it disappears. SHARK-321, 328 : Syslog is not working when TCP/IP mode is chosen. SHARK-338 : Add new language in LCD. SHARK-340 : In Web pages, set a new time doesn't modify each fields. SHARK-345 : Web pages in SSL mode could cause White page and reboot card. SHARK-346 : Some data configuration (Hostname, dhcp and daisychain config) are duplicated on EPDU. SHARK-347 : Some errors on Input and Group Energy (kWh). SHARK-350 : Data corruption could cause no access to the card. SHARK-353 : Not possible to login with an authentication by LDAP digest Md5. SHARK-366 : Sorting function dos not work correctly in Logs menu. SHARK-367, 373 : In Chrome browser, some messages displayed in a window were misaligned SHARK-370 : Branch name could be lost due to the space character. SHARK-371, 359 : SCOB locks/restart after ~ 150 login. SHARK-386 : Internal Error 103075 due to Periodic email. SHARK-389 : Input phase name is different between Web pages and LCD. /================================================================/ Firmware Version: 00.00.0024 Changes since version 00.00.0023 : ---------------------------------- - SHARK-360 : CLI commands get, info, banner and prompt buffers now use the stack rather than the heap to avoid fragmentation and the occurence of the internal error code 3075(0xC03). - SHARK-347, SHARK-336 : Provisary fix by Eeprom backup read in RAM. Calculate the Total energy counter by cumulate directly the phase registers rather than cumulate the HID data (minus the stub in eePROM). Eeprom driver Write function manage the mutex correctly. /================================================================/ Firmware Version: 00.00.0023 Changes since version 00.00.0022 : ---------------------------------- - Fix the JIRA tickets from JIRA Validation : SHARK-345 : SSL White page and SCOB restart. (back to the setup of SSL parameters of SP7). SHARK-348 : Syslog messages can't be read on server if a Hostname is available. SHARK-349 : Add a filter, at least 3 consecutive SLIP request fails before set the alarm PDU internal com failure. /================================================================/ Firmware Version: 00.00.0022 Changes since version 00.00.0021 : ---------------------------------- - Add the syslog feature. - Add the Power schedule objects in XML and Web page (but not applied to the outlets). - 4 more Languages : French, Spanish, German, Korean. - Change the default value of System.Network.Authentication.MaxSessionTime to 1800 sec. - Fix the JIRA tickets from JIRA Validation : SHARK #326 : Fix issue of IMP/XMLM service compatibility failure SHARK #324 #315 #305 #292 #264 : - Increasing robustness of the CAN upload. - Improve Daisy chain to avoid the Internal Error and lock issue : SHUT thread priority set to 10 (same as DC thread) to avoid inter blocking. CAN : enable the automatic bus-off management. Init HID table of DC device : Fix the length not managed that could occur HID_BAD_REPORT. SHUT suppress a modif of build 21 that could manage the report 253(Discovery) as a report of data PDU then make a HID_BAD_REPORT internal error. Iterate 3 times a request if no answer (allow to cleanup the Log of some "Daisy Chain device does not answer" events). - HID_ACQ_CYCLE internal error put in comment because it's notified by com error with Teridian. SHARK #309 : Read only user cannot display the LDAP page SHARK #308 : SSL redirect page display HP informations. SHARK #306 : EMP issue with dry contact alarm and measurement, with no EMP. SHARK #298 : Fix email wrong label with HP. SHARK #294 : SCOB F/W upgrade infinitive loop (to be tested) SHARK #322 : Syslog feature param are applied on Line (without restart SCOB) SHARK #336 #337 : Energy in HID Statistic[5] in Wh (not kJoule) make there is no overrun. SHARK #144 : Device Termination issue after Discovery. - Other fixes : Fix recovery superadmin login/password . criteria is now on both login and password. Fix test on value returned by xmlExpatRamConfiguration : 0 means file parsing OK, != 0 otherwise. Energy in HID Statistic[5] Alarm PDU.Gang[x].PresentStatus.Tripped /================================================================/ Firmware Version: 00.00.0021 Changes since version 00.00.0020 : ---------------------------------- - Add the syslog feature. - Add the Power schedule objects in XML and Web page (but not applied to the outlets). - Now 6 Languages : English, Chinese Simp, Chinese Trad, Japanese, Portuguese, Czech. - Energy in HID Statistic[4] are now in Wh(not kJoule). - Change the default value of System.Network.Authentication.MaxSessionTime to 1800 sec. - Fix the JIRA tickets from JIRA Validation : SHARK #292 : Fix issue of acknowledgment expected in case of upload, and discovery requests were not completely stopped. - Fix the QUIX items : QUIX 1001293991 : Unified font-family to 'tahoma' on all ExtJs components (tree, button, grid, field label) QUIX 1001294255 : Big amounts of Wh not report correctly, now each counter can manage up to 2147483647 Wh. QUIX 1001301303 (SHARK-286) : Suppress the repetition of Outlet and Section in the alarm description. - Other fixes : "Active Power" column blanked when value is 0. Upgrade F/W from Web add authentication parameters in the url. /================================================================/ Firmware Version: 00.00.0019 Changes since version 00.00.0018 : ---------------------------------- - Add the remote authentication through RADIUS, see Web page RADIUS. - SNMP traps of the Mib ePDU Eaton fully integrated. - Add a Web link to Open Sources Licenses text file in the PDU informations panel. - In mode daisy chain, Upgrade the host F/W also upgrade the device. - The LCD menu to select the language is avilable. - Fix the JIRA tickets from JIRA Validation : SHARK-203 : Fix LCD Factory default confirm 'Cancel' truncated. SHARK-265 : Fix management of authorized range value for threshold settings sections and outlets. SHARK-252 : Add Time Synchronization between Master and Slave, When the PDU host restarts, when the PDU host receives a new datation (in manual or NTP mode, when the PDU host discovers a device. SHARK-285 : Unauthorize TCP/IP Hostname spacing. - Fix the QUIX items : QUIX 1001303596 (eq. SHARK-260) : SNMPv1 & SNMPv3 user names can't be duplicated. QUIX 1001295903 (eq. SHARK-247) : Dry Contact 1 information cannot change when EMP is plugged on PDU Slave. QUIX 1001294510 (eq. SHARK-278) : Telnet Data chopped off and data not matching. QUIX 1001296509 (eq. SHARK-248) : Bad Display for Temperature values in Alarm menu / Kelvin. QUIX 1001296762 (eq. SHARK-276) : SSL mode upload PDUconfiguration file. QUIX 1001298953 : In page Overview, Remove Alarm status in the outlet tooltip for MI and SW PDU. Add the alarm icon in the Voltage phase. - Other Fix : Daisy chain PDU Master MA can manage PDU Device MI. Add a parameter and web checkbox that enable/disable the certificate in LDAPS/TLS bind. Now events below apperas in the log file : Environment.Input[1].PresentStatus.State Environment.Input[2].PresentStatus.State Environment.PresentStatus.Present PDU.OutletSystem[1].Outlet[x].PresentStatus.SwitchOnOff A few issues fixed in the ePDU Eaton Mib : groupControlStatus, groupBreakerStatus. The PDU Configuration file that concerns another part number than the current one in SCOB is deleted, then a new one is created with the default values. Improve the Outlet web page for Managed PDU. Change length of user name: from 15 to 50. Add Eaton logo for the redirect web page in ssl mode. Improve the environment web page. Improve the synchro of task HID and SLIP, Change priority of SLIP task. More details with OS internal error log 101282. /================================================================/ Firmware Version: 00.00.0018 Changes since version 00.00.0017 : ---------------------------------- - Fully Tested on SHARK MA ePDU. - Fix the QUIX items : QXCR1001290359 (eq. SHARK-234) : Change the header of the log file. QXCR1001293092 (eq. SHARK-235) : Change the Time up format. QXCR1001293675 : Warning to restart the cad when changin Security->Global parameters. QXCR1001293678 (eq. SHARK-232) : Change the place of event card restart in the Log. QXCR1001293991 (eq. SHARK-231) : Change the font of banner and bottom web page. QXCR1001293997 : The web page banner shows the type of PDU. QXCR1001294031 : Take care that all fields in web page appears correctly for resolution 1024 * 768. QXCR1001294255 (eq. SHARK-237) : Energy counters through Web, CLI, SNMP are consistent. QXCR1001295684 (eq. SHARK-242) : Sort labels in the web page Logs are translated in Japanese. QXCR1001296165 : Fixed date/time issue in the mail body sent by host for a PDU daisy chained device. QXCR1001296190 : Check that On the 3 groups of PDU[1], modify and save some voltage thresholds make alarms appearare generated and PDU does not restart. QXCR1001296429 : Log message fixed when factory reset from LCD. QXCR1001296727 : Fix for high voltage range (>=264 v), the defaut low critical and low warning thresholds. QXCR1001300657 : Fix the card restart issue when Testing the mail recipient associated to the superadmin. - Fix the JIRA tickets from JIRA Validation : SHARK-245 : Fix the environment gauge tooltip now shows Humidity label and Temperature label. SHARK-229 : All save action from web pages are followed by a pop up saving successfull. SHARK-251 : Add units for Current and Active power in the Overview web page. SHARK 240 : Group Voltage Default values was returned not with the pduId parameter but with the constant value LOCAL_PDU SHARK-261 : Check size of Contact and Location and fix overlap buffer in cgiPduInformation. - Suppress provisory the authentication security on config/get_object.xml service. - Web interface Improvments : Improve the Environment page for Daisy chain notably. Remote group name max length goes to 49 characters for Shark and stays to 15 characters for Glandore. LDAP : "Search User", "User Base DN", and "UPS Group Base DN" fields goes to 249 characters (99 characters before). - A few modications about LDAP : From filter and OpenLDAP Server, keep coma in the unescape filter function. Correction in filter to manage coma escape used by AD. Add better LDAP Server CA management. - Fix an indexing issue when controlling the outlets Off and On from the web Group page. - Fix some Teridian LED management issues. - Fix issues in EATON ePDU Mib wrapping. - Fix Toggle control that was not launched. - Improvement of the "CAN Discovery" functionality. - Fixes the issue when the CAN ID is modified on the host screen after a discovery. The SHUT CAN task of the device was frozen and not reseted. - Fix the issue in the recovery of the parameter that are of type scalar coded as below "xx|yy|.." now works well even for the iteration that follow en empty place. - Crypt the data below in the Conf data file : System.Network.SNMP.V3.User[x].Password System.Network.SNMP.V3.User[x].PrivacyKey System.Network.SmtpServer.Password - Fix a possible deadlock in between threads configTask and Httpd that blocked each other with the mutex MUTEX_BASIC and MUTEX_NETWORK. - Add the command set System.EepromBackup.Reset that allows to reset the whole Eeprom backup zone (in case of Energy counters cannot be displayed). /================================================================/ Firmware Version: 00.00.0017 Changes since version 01.00.0016 : ---------------------------------- - Build for SHARK ePDU. - SNMP fully integrated with Mib Eaton (without traps). - Integration of Daisy Chain 3+1. /================================================================/ Firmware Version: 01.00.0016 Changes since version 00.00.0015 : ---------------------------------- - Fix JIRA SHARK-209 : Pb when editing the user email. The email settings windows load the data in the wrong user list. - On SNMP web page, refer to the CPQPOWER.Mib download. - Add the directory web\data into the FS that contains the CPQPOWER.Mib - Modify the hp_logo.gif with the file send by Matt in his email (title:"Glandore Firmware" date:28/06/2013). - Fix the issue of "Internal error 1283" in case of losing communication with CAN device. - Adjustment of Daisy Chain and Shut timeout. - Increasing of the stack size of LOG_FS task. - LCD Bug Fix: SHARK-214: Invert arrows behaviour when the LCD rotation is configured with 180° or -90°. - Increase the Quadnet Heap to allow malloc in SSL mode. - Fix ticket SHARK-212 issue where PDU[0] is in the mail body instead of PDU[1] - LCD screensaver improvement: Display data at the center of the screen. - The command System.Restart only launch a restart (no update of configuration files). - Fix SHARK-220 (Max current will not over 65535 mA). - Max socket changed from 32 to 24. - In SSL mode, socket buffer reception end emission are changed from (2*1460) to 4096, That makes HTTPS run more quickly(Ex : shark.js takes 5 sec before, 3.5 sec after). - Fix ticket SHARK-210 : workaround that deletes the log file when it cannot be open. - Fix JIRA SHARK-222 : Bug in cgi_alarmCount request response in daisy chain when analyzing the alarms for the slave devices. - Fix ticket SHARK-223 issue: Daisy Chain PDU[1] e-mail dating problem. - Fix ticket SHARK-201 : LCD button freeze. - Fix ticket SHARK-224 : Outlet type label added for nemaL715 (29), rf203p277 (30). /================================================================/ Firmware Version: 00.00.0015 Changes since version 00.00.0014 : ---------------------------------- - Fix ticket SHARK-202 where the SCOB card init delayed of 2 minutes when no Ethernet cable connected. - Change label ePDU with PDU on the LCD. - Add the icon for active alarms in the left navigation bar (when no alarms). - Increase the Gateway to Teridian Write time out from 5 sec to 15 sec - Fix the value returned by the gateway command that was value expected minus 1. /================================================================/ Firmware Version: 00.00.0014 Improvements since version 00.00.0013 : --------------------------------------- - Fix the JIRA tickets from JIRA Validation : SHARK-138 : Fix the message displayed by Web when user with no access tries to Log SHARK-156 : Fix security leak on get_object.xml and set_object.xml SHARK-162 : Fix card reboot when sending CLI command on SNMP V3 settings SHARK-168 : The trap test button is greyed when the trap is diasbled and No events. SHARK-175 : The logs are well ordered. SHARK-176 : The value of the SMTP port is well saved and is taken in account when sending a request to the SMTP server. SHARK-179 : Improve the size of web files. SHARK-183 : Improve PDU com failure alarm label . SHARK-185 : Fix issue on web settings page of LDAP servers. SHARK-187 : Fix sensor meters does not appear on LCD. SHARK-189 : Fix Nor flash access conflict in between erase/write in Flash and eecution of code. SHARK-190 : Fix trap number missing. SHARK-192 : Upload and Upgrade button are greyed when the card works in HTTPS. SHARK-195 : Link on blank fields are accessible. SHARK-195 : Fix modyfing the name of outlet by Web in conf daisy chain. - Fix the JIRA tickets from JIRA Firmware : SHARK-32, SHARK-184 : Fix the Power factor negative value SHARK-157 : Energy data are returned in Wh. SHARK-160 : Fix history does not show the last alarm on LCD. SHARK-163 : No alarms now appear on LCD. SHARK-167 : Display LCD rotation not rest by factory reset. SHARK-170 : Phase alarm labels in LCD SHARK-171 : Fix Default values of gang iName. SHARK-172 : Fix the PDU 1 hroup not shown on Web. SHARK-178 : Fix default button in settings dry contacts web page. SHARK-191 : Fix huge values issue by acquring Teridian values. - Update Japanese translation. - Change ePDU label with PDU. - CLI improvements : Becomes not case sensitive. info command shows now details on every data. Banner name. - Add the superuser login/password recovery procedure through CLI serial. - Groups measurement settings, when records from differents pdu are selected, set the maximum current to the lowest value between the impacted pdu. - Fix the issue where FTP failed to access the File system when SSL is activated. - Suppress the double log login fail in case of a remote user login successfully. - Add some USER logs when a user login or logout by Web or CLI. - Add some USER logs when a user login or logout by FTP. - By modify the configuration of a daisy chained device PDU from the host, then the new setting is saved into the ConfigurationPdu file inside the device PDU. - Improve a few data of the CPQPower Mib and CpqHost Mib. - Timestamp the alarm PDU.PowerSummary.PresentStatus.CommunicationLost. - On Driver Ethernet, report a modification From Nemo that improves the Ethernet link detection. /================================================================/ Firmware Version: 00.00.0013 Improvements since version 00.00.0012 : --------------------------------------- - Correction of authentication for LDAP method SASL Digest MD5. /================================================================/ Firmware Version: 00.00.0012 Improvements since version 00.00.0011 : --------------------------------------- - Add Mail Notification and SMTP settings. - SNMP : trap return to normal is sent, Group type value is fixed. - Ports can be configured for SNMP, SMTP, HTTP, HTTPS, Telnet, SSH. - LDAP method SASL Digest MD5. - Environment settings full implemented. - Language English/Japanese for Web pages and alarm/Log messages. - At Initialisation parameters IPv4 and IPV6 below are restored from EEPROM savings, that allows not to overwrite these parameters when duplicating the card parameters file from one SCOB to another. System.Network.IPAddress System.Network.IPGateway System.Network.IPMask System.Network.IPv6LocalAddress System.Network.PrefixLength1 System.Network.IPv6DefaultGateway - Fix the JIRA tickets below : SHARK-128 : Display orientation can be changed, but comes back to original orientation after card restart. SHARK-152 : Master web page corrupted SHARK-157 : Energy Measurements Total Input Incorrect. SHARK-158 : Max Power and Max Current Statistics have "Occurred on" and "Since" data swapped. SHARK-161 : Web Navigation Bar repeats Overview section when Environment is selected. SHARK-164 : No detection of Circuit breaker on MI PDU. SHARK-165 : Date and time incorrect in web page Active Alarms. SHARK-169 : Trap object sending 'clear alarm' not sending /================================================================/ Firmware Version: 00.00.0011 Improvements since version 00.00.0010 : --------------------------------------- - SNMP fully integrated with Mib CPQPower and traps. /================================================================/ Firmware Version: 00.00.0010 Improvements since version 00.00.0009 : --------------------------------------- - Fix the JIRA tickets below : SHARK-95 : Web page stuck SHARK-121 : SCOB reset when no alarm in LCD alarm menu. SHARK-137 : Daisy chain host detection unstability. SHARK-142 : PDU user cannot change its password from web page. SHARK-145 : No more need to reset the board when the daisy chain behavior is modified. /================================================================/ Firmware Version: 00.00.0009 Improvements since version 00.00.0008 : --------------------------------------- - New management of leds. - Fixes the issue of the CAN termination. - Improve the firmware upgrade feature. - Fix the JIRA tickets below : SHARK-77 & SHARK-92 : Power factor not stable for Input. /================================================================/ Firmware Version: 00.00.0008 Improvements since version 00.00.0007 : --------------------------------------- - Upload firmware+Filesystem thru the file Image*.bin via FTP and HTTP. - New folders in the file system : config contains the Configuration file, the SSH key and the log file. config/hw contains the UCF file. eaton, eaton/config and /ws folder no more exist. - Add the Sensor acquisition, see Web page Environment. - Add the Account management, see Web page Access Accounts - Add the SNMP user management, see Web page SNMP. - Add the Security parameters. - Add the remote authentication through LDAP, see Web page LDAP. - Add the session management for rs232, Telnet, SSH or Web connection; - Takes in account the level and security rights of the connected login. - A part of the Firmware is now located in External Flash. - Add the SSH feature from Mocana stack for secured CLI. - Fix the JIRA tickets below : SHARK-46 : Factory Reset since LCD is activated. SHARK-77 : Power factor not stable for Gang. SHARK-91 : Init RAM of LCD controler that avoid the LCD grainy at some startup. SHARK-94 : Sort function simplified in logs and alarms. SHARK-96 & SHARK-97 : Check the threshold Low Critical